Vicot's gas absorption heat pump system uses natural gas as a clean driving energy. It uses MR717 as the refrigerant, and water as the absorbent, then, using a fin heat exchanger, it can extract the low grade heat energy from the air. Its heating efficiency is 1.8 times better than gas boiler available on the market today, making it an efficient piece of energy utilization equipment.
The gas fired absorption heat pump is divided into the heating unit and hot water unit, both of which are suitable for common heat requirement locations likes schools, other public buildings and residential spaces.
Item | Standard heating conditions | ||
Nominal heating capacity | 64 kW | ||
Water flow rate | ≥5 m3/h | ||
Pressure drop | ≤70 KPa | ||
Min water input temperature | 9°C | ||
Max water outlet temperature | 65°C | ||
Environment temperature | MAX | 20°C | |
MIN | -30°C | ||
Rated heating input power | 33 kW | ||
Heating input power setting range | 14-37.7 kW | ||
Rated natural gas Plow | 3.5 m3/h | ||
Natural gas Plow setting range | 1.5-4.0 m3/h | ||
Power | 380V/3Ph/50Hz | ||
Electric input power | 1.25 kW | ||
Machine unit weight | 1250 Kg | ||
Noise | 54 DB(A) | ||
Size of connecting pipe | Water pipe | G11/4(DN32) In | |
Natural gas pipe | R1/2 In | ||
Dimension (L*W*H) | 2380*1380*2200 mm |
Index
air heat, absorption heat pump, solar thermal
Vicot Group
Factory Location: Hongdu Road, Dezhou Economic Development Zone, Dezhou City, Shandong Province
Add. (Imp. & Exp. Office): A1, 4th Floor, Building 2, Shuntai Plaza, Jinan Innovation Zone, Jinan City, Shandong
Tel: +86-531-88255580
+86-531-88255563
Fax: +86-531-88255591
Email: export@vicot.com.cn
Website: www.vicot.com.cn